SECTION 09547
MODULAR WOOD CEILING SYSTEM
PART 1 - GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of Contract including General and Supplementary Conditions.
1.02 SUMMARY
A. This section describes the requirements for providing the suspended wood ceiling systems as indicated on the drawings and specified, to include:
1. Modular wood ceiling panels
2. Modular suspension assemblies
3. (Optional) Perforations
4. (Optional) Sound absorbing materials
5. Accessories; provide all other necessary items including devices for attachments to overhead construction, secondary members, splines, splices, connecting clips, wall connectors, wall trims and all other devices required for a complete installation.
6. Coordinate items penetrating or being integrated into ceiling systems with responsible trades.
1.03 Quality Assurance
A. Reference Standards:
1. American Society for Testing and Materials (ASTM):
a) C635 Specifications for Metal Suspension for Acoustical Tile and Lay-In Panel Ceiling.
b) C636 Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels.
c) All woodworking materials shall meet the requirements of the Architectural Woodworking Institute. (AWI) AWI and/or WIC.
d) Material Tested per ASTM E-84 Class 1 per U.B.C
2. Local Building Code, current edition requirements.
1.04 Submittals
A. Comply with the requirements of Division 1, Section 01300, Submittals.
B. Product Data: Submit manufacturer's product descriptions and specifications for wood ceiling system.
C. Samples: Submit full size ceiling panel minimum of 12" long showing straight edge detail with an attached suspension system and perimeter trim member in the specified finish.
D. (Optional) Mock-up: Submit a full size production quality ceiling panel for an area of 10' x 10'. Mock-up shall include all required accessories for a complete installation, including suspension and trims.
E. Shop Drawings:
1. Provide properly dimensioned shop drawings showing ceiling layout. Show all locations, markings, quantities, materials, sizes and shapes and indicate all methods of connecting, anchoring, fastening, bracing and attaching to work of other trades. Shop drawing submittals to be on computer aided design systems and furnished on computer disks. System shall be compatible with that of the architect.
PART 2 - PRODUCTS
2.01 MATERIALS
A. Project design is based on materials and systems of Ceilings Plus, Los Angeles, CA 800-822-3411, www.ceilingsplus.com.
Other manufacturers must be approved prior to the bid in written form, by the architect. Specified manufacturer's standard of quality and manufacturing tolerances shall be criteria for evaluating "equivalent" product.
2.02 MODULAR WOOD CEILING PANELS
A. Modular Wood Panels, "Runways" by Ceilings Plus with Arboreal Wood Veneer Finish
1. Panel Construction: The ceiling panels are to be die formed from a single sheet of primed aluminum and 1/32 thick wood veneer face. The panels to be formed with a minimum 1-1/4" integral return edge on all panel sides. No indentations, marks or defacing of the exposed surface of the wood ceiling panel will be allowed. The primed porous aluminum panels shall be formed in adequate thickness and factory formed to specified dimensions.
2. Adhesion: The adhesion shall be formaldehyde free with a cross linked emulsion . The primed aluminum properties shall included, high shear strength, with adhesion levels greater than 8lbs per square inch.
3. Veneer: All exposed surfaces of the veneer shall be finish sanded with 600-grit sandpaper between sealer and finish coat. The wood veneer specie shall be 3 face on (all exposed faces). Veneer shall be as selected by the architect. Range of veneer grain and color to be submitted for approval. The panels will be finished with a clear, two-step sealer and topcoat.
4. Perforations. (Optional) Perforations per architect selection. Panels to have a solid margin, non perforated, on all sides.
5. Sound absorbing material. (Optional) to be a gray, black or white, non-woven fabric with Class 1 fire rating. Perforated panels with absorbing material to achieve an N.R.C. of .70-.80 minimum.
B. No fasteners of any kind shall be visible on exposed face surfaces of ceiling panels or support tees. Down light openings and sprinkler holes shall be factory precision cut as required.
C. The plenum shall be 100% accessible. Every panel must be removable. Progressive panel access is not acceptable. Heavy duty torsion springs and clip assemblies to be mounted to every panel for downward access, without potential for damage to panel face or hinge assembly. Hinge assembly shall be attached to panel with minimum 2 flush fasteners. Attaching torsion spring directly to panel with fastener will not be accepted.
D. Fire tests. Complete system test including suspension, primed aluminum and veneer with finish shall meet ASTM E84 Class I. Flame spread 20.
2.03 SUPPORTING GRID
A. Supporting grid system shall consist of straight, factory formed tee in adequate thickness, to support loads. Finish tee to be matte black where exposed. Tee shall be factory slotted to accept torsion spring attachment.
B. Ceiling suspension shall meet structural requirements as required in ASTM 635, ASTM 636, heavy duty direct hung ceilings.
C. Hanger attachments shall be 12 ga. pre-straightened steel wires, rods or other approved hanging device that will support required loads.
D. Tolerances: Maximum deviation of ceiling panels from edge to edge in width shall not exceed 1/4" in 10' when measured with a straightedge placed at any directional location on the finished surfaces. Maximum deviation shall not exceed 1/4" from level in any area or room.
PART 3 - EXECUTION
3.01 INSPECTION
A. General Installation:
1. Materials shall be installed in strict accordance with procedures recommended by the manufacturer and requirements of agencies having jurisdiction. All materials for this section shall be from a single source ceiling manufacturer with minimum 5 years experience with products of the nature specified.
2. Attach supporting channels of adequate strength to construction above by approved connection method according to local building codes.
3. The contractor responsible for the work of this section shall be qualified and experienced in the performance of this work and done so for no less than a period of 5 years.
B. Product Handling
1. Delivery: Deliver metal ceiling components to job site in unopened containers identified with product manufacturer's name, trade name and other applicable identification.
2. Storage: Store and install material in areas with a relative humidity not exceed-55% and a temperature range of 65 - 75 degrees F. Store away from direct sunlight. Install when space is completely conditioned, clean and free of airborne particles.
3. Remove protective film material from panels only when space is completely clean and dust free of airborne particles. Cotton white gloves shall be used for final installation.
4. Remove and replace units that have been damaged or cannot be satisfactorily cleaned to the owner's or architect's acceptance, at no additional cost to the owner. To clean materials follow manufacturer's written cleaning procedures.
C. Maintenance
1. Maintenance instructions, as written by the manufacturer,
are to be left with the building owner.